2 lenze brake resistors, 1 rated data, Lenze brake resistors – Lenze EVF9383 User Manual

Page 429: Rated data, Braking operation

Advertising
background image

Braking operation

Lenze brake resistors

Rated data

12

12.2

12.2.1

l

12.2−1

EDSVF9383V EN 7.1−04/2012

12.2

Lenze brake resistors

12.2.1

Rated data

Field

Data

Resistance R

15

W

Continuous power

1)

4.0 kW

Thermal capacity

600.0 kWs

Switch−on cycle

Braking for max. 19/15/14/11 s, then at least
131/135/136/139 s break

2)

Cable cross−section to be
connected

6 mm

2

AWG 10

Mass

12.5 kg

Order No.

ERBD015R04K0

Observe the national and regional legislation

1)

The continuous power is a reference value for the selection of brake resistors. Braking at peak
brake power (V

2

DC

/R).

2)

More information on the switching threshold V

DC

(685 V, 755 V, 785 V, 885 V) of the brake

transistor can be found in chapter 12.1

)

Note!

As standard the brake resistor is equipped with a temperature
switch (NC contact max. AC 250 V, 0.5 A).

Advertising