Configuration

Code table

8

8.5

l

8.5−60

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0970

s

CFG: SET

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Starting value for the
controlled deceleration in [%]
of C0011

See System
Manual
(extension)

C0971

s

CFG: FAULT

1000 FIXED0

^ Selection list 2

Configuration of digital input
signal, function block MFAIL

l

HIGH = activates mains failure
control

C0972

s

CFG: RESET

1000 FIXED0

^ Selection list 2

Configuration of digital input
signal, function block MFAIL

l

HIGH = resets mains failure
control

C0973

s

CFG: ADAPT

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Dynamic adaptation of the
proportional gain of U

Gsetl

controller in [%] of C0980

C0974

s

CFG: CONST

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Proportional gain of U

Gset

controller in [%] of C0980

C0975

s

CFG:
THRESHLD

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Restart protection when the
value falls below the speed
threshold

l

Restart threshold in [%] of
C0011

C0976

s

CFG: NACT

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Comparison value for the
restart threshold in [%] of
C0011

l

Start for V

2

controller

C0977

s

CFG: SET

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Speed starting value for the
deceleration in [%] of C0011

C0978

s

CFG: DC−SET

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block MFAIL

l

Setting of the voltage setpoint
on which the DC−bus voltage is
to be kept (100 % = 1000 V)

C0980 MFAIL Vp

0.500 0.001

{0.001}

31.000 Gain V

p

, function block MFAIL

See System
Manual
(extension)

C0981 MFAIL Tn

100

20

{1 ms}

2000 Integral−action time T

n

, function

block MFAIL

C0982 MFAIL Tir

2.000 0.001

{0.001 s}

16.000 Acceleration time T

ir

, function

block MFAIL

C0983 Retrigger T

1.000 0.001

{0.001 s}

60.000 Retrigger time, function block

MFAIL

l

After the time has elapsed, the
mains failure control is
terminated