Configuration, Code table – Lenze EVF9383 User Manual

Page 323

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−35

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0582 MONIT OH4

2

2

Warning

Configuration monitoring OH4,
heatsink temperature

l

The operating temperature can
be set in C0122

See System
Manual
(extension)

3

Off

C0583 MONIT OH3

3

0

TRIP

Configuration of motor
temperature monitoring with
fixed operating temperature

l

Only for KTY at X8

l

The operating temperature is
fixed at 150 °C

^
6.6−10

See System
Manual
(extension)

2

Warning

3

Off

C0584 MONIT OH7

3

2

Warning

Configuration of monitoring
motor temperature with variable
operating temperature

l

Only for KTY at X8

l

When reaching the
temperature set in C0121 the
warning OH7 is activated

^
6.6−10

See System
Manual
(extension)

3

Off

C0585 MONIT OH8

3

0

TRIP

Configuration of motor
temperature monitoring

l

Temperature monitoring via
PTC input (T1, T2)

^ 6.6−8

See System
Manual
(extension)

2

Warning

3

Off

C0587 MONIT SD3

3

0

TRIP

Configuration of monitoring SD3,
encoder at X9

l

Monitors the voltage supply at
X9/pin 8

See System
Manual
(extension)

2

Warning

3

Off

C0588 MONIT

H10/H11

0

0

TRIP

Configuration of monitoring H10
and H11, thermal sensors in the
controller

l

H10: Sensor error − heatsink
temperature

l

H11: Sensor error − interior
temperature

See System
Manual
(extension)

3

Off

C0591 MONIT CE1

3

0

TRIP

Configuration of monitoring CE1,
communication error at CAN−IN1

See System
Manual
(extension)

2

Warning

3

Off

C0592 MONIT CE2

3

0

TRIP

Configuration of monitoring CE2,
communication error at CAN−IN2

2

Warning

3

Off

C0593 MONIT CE3

3

0

TRIP

Configuration of monitoring CE3,
communication error at CAN−IN3

2

Warning

3

Off

C0594 MONIT SD6

3

0

TRIP

Activation of the motor
temperature monitoring with KTY
at X8

l

Use C0594 = 0 or 2 to activate
monitoring

l

In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated

l

Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature

in C0583

– Variable operating

temperature in C0584

^
6.6−10

See System
Manual
(extension)

2

Warning

3

Off