Danger – Lenze EVF9383 User Manual

Page 91

Advertising
background image

Basic devices in the power range 250 ... 400 kW

Fan connection 400/500 V devices

5.5

5.5.6

l

5.5−9

EDSVF9383V EN 7.1−04/2012

{

Danger!

When the fan is externally supplied with voltage, the terminal L2
carries dangerous mains voltage!

When the controller is supplied via the DC bus, the fan must be separately
supplied with mains voltage (see

1). In this case, the bridge between the

terminals 102 and 103 must be removed (see

0).

Remove bridge

Mains connection for the operation of the fan on

AC 340 ... 440 V

AC 440 ... 577 V

101

102

103

104

}

0

L1

L2

AC 340 … 440 V

101

102

103

104

1

L1

L2

AC 440 … 577 V

101

102

103

104

1

L1

L2

9300vec160

9300vec046

9300vec047

In case of an external voltage supply the fan is protected by a fuse integrated
in terminal 104.

101

102

103

104

L1

L2

0

1

9300vec161

Fig. 5.5−10

Fusing of the fan

0 Open the fuse holder.

1 Remove the defect fuse from the support and replace it by the following

type:
Type:

500V SA 2A 6.32

Ref. no.:

P098131

Manufacturer: Ferraz Shawmut

Fan connection when
controller is supplied via the
DC bus

Exchange defect fuse