Safety engineering

Functional test

Important notes

11

11.4

11.4.1

l

11.4−1

EDSVF9383V EN 7.1−04/2012

11.4

Functional test

11.4.1

Important notes

}

Danger!

Unexpected start−up of the machine possible
The "Safe torque off" safety function provides protection against
an unexpected start−up of the drive and therefore is an
important item within the safety concept for a machine. It has to
be ensured that this function works correctly.
Possible consequences:

ƒ

Death, severe injury, or damage to material assets, when the
safety function fails.

Protective measures:
After the installation and at regular intervals, the operator has to
check the function of the "Safe torque off" circuit.

ƒ

When doing this, check both disconnecting paths separately
with regard to their disconnection capability.

ƒ

The functional test can be carried out manually or
automatically via the PLC.

ƒ

Basically the inspection interval depends on the application
and the corresponding risk analysis, as well as on the system
as a whole. It should not exceed 1 year.

ƒ

If the functional test shows impermissible states,
– the drive or the machine has to be shut down immediately.
– commissioning is not permitted until the safety function

operates correctly.