Safety engineering, Danger – Lenze EVF9383 User Manual

Page 418

Advertising
background image

Safety engineering

Safety relay K

SR

11

11.3

l

11.3−2

EDSVF9383V EN 7.1−04/2012

}

Danger!

Faulty operation in case of earth faults possible
The correct functioning of the safety function is not ensured if an
earth fault occurs.
Possible consequences:

ƒ

A failure of the safety function can lead to death, severe
injuries or damage to material.

Protective measures:
The electrical reference point for the coil of the safety relay K

SR

must be connected to the PE conductor system (EN 60204−1,
paragraph 9.4.3)!

Terminal strip X11

Internal wiring / wiring of terminal strip X11

3 4

3 3

K 3 2

K 3 1

34
33

K

32

K

31

DC 24 V

X11

34
33

K32

K31

+5 V

+

+

K

SR

9300vec103

Fig. 11.3−1

Safety relay K

SR

Terminal

Function
Bold print = Lenze setting

Level / state

Electrical data

X11/K32
X11/K31

Safety relay K

SR

1st disconnecting
path

Feedback − pulse inhibit

Open contact: Pulse inhibit is
inactive (operation)

See technical data of the
safety relay K

SR

Closed contact: Pulse inhibit is
active

X11/33

– coil of safety relay K

SR

Coil is not carrying any current:
pulse inhibit is active

X11/34

+ coil of safety relay K

SR

Coil is carrying current: pulse
inhibit is inactive (operation)

X5/28

Controller inhibit
(DCTRL−CINH)
2nd
disconnecting
path

Controller enable/inhibit

LOW: Controller inhibited
HIGH: Controller enabled

LOW: 0 ... +3 V
HIGH: +12 ... +30 V

Input current at +24 V:
8 mA

Reading and processing
the input signals − 1/ms
(mean value)

Wiring