Safety engineering

Functional test

Monitoring the safety function with a PLC

11

11.4

11.4.3

l

11.4−3

EDSVF9383V EN 7.1−04/2012

11.4.3

Monitoring the safety function with a PLC

K

SR

µC

PWM

PWM

RFR

DC 24 V

Z1

9300

S1

S2

IN 1

IN 2

IN 3

IN 4

X11/34

X11/33

X11/K32

X11/K31

X5/28

DIGOUT

9300vec104

Fig. 11.4−1

Circuit diagram for monitoring the safety function with a PLC

S1, S2

Separate disconnection options of the two disconnecting paths

K

SR

Safety relay

X11/34

Safety relay control

X11/33

Safety relay control (GND)

X11/K32 Forcibly guided feedback contact (24 V)
X11/K31 Forcibly guided feedback contact
DIGOUT

Digital output for evaluating the motor current

X5/28

Controller inhibit

Z1

Programmable logic controller (PLC)

IN 1 − 4

Digital inputs

The following conditions must be met:

ƒ The PLC must be programmed such that the complete system is set to a

safe state immediately when the function check leads to an
impermissible state.

ƒ The parameter setting of a digital output must be such that you can

conclude to the output current I

motor

of the drive (see parameterisation

example).