Configuration, Code table – Lenze EVF9383 User Manual

Page 291

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−3

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0010 N

min

0

0

{1 rpm}

36000

l

Reference value
for the absolute
and relative
setpoint selection
for the
acceleration and
deceleration
times

l

C0059 must be
set correctly

l

Set C0010 <
C0011

l

C0010 is only
effective in case
of analog setpoint
selection via AIN1

Important: For
parameter setting
via interface, major
changes in one step
should only be made
when the controller
is inhibited.

Minimum
speed

^
6.10−1

C0011 N

max

3000 0

{1 rpm}

36000

Maximum
speed

C0012 Tir (acc)

5.00

0.00

{0.01 s}

9999.90 Acceleration time T

ir

of the main

setpoint

l

Refers to speed change
0 ... C0011

^
6.10−3

C0013 Tif (dec)

5.00

0.00

{0.01 s}

9999.90 Deceleration time T

if

of the main

setpoint

l

Refers to speed change
0 ... C0011

C0014 V/f charact.

0

Characteristic in the V/f
characteristic control mode

^
8.2−25

0

Linear

Linear V/f characteristic

1

square

Square V/f characteristic

C0015 Rated freq

50

10

{1 Hz}

5000 V/f−rated frequency

In C0015 you can set a base
frequency which differs from the
rated motor frequency (C0089)

l

Lenze setting: C0015 = C0089

l

Changing C0086 or C0089
overwrites the value in C0015

^
8.2−25

C0016 Umin boost

0.00

0.00

{0.01 %}

100.00 U

min

boost (FCODE)

l

C0016 = 1 % corresponds to a
boost of 1 % of the rated motor
voltage (C0090)

l

Code is freely configurable

^ 6.8−4

C0017 FCODE (Qmin)

50

−36000

{1 rpm}

36000 Q

min

−switching threshold (FCODE)

l

Programmable speed threshold

l

If the current speed is < C0017,
CMP1−OUT is activated.

l

Freely configurable code

Advertising
This manual is related to the following products: