Lenze EVF9383 User Manual
Page 233
Advertising
Configuration
Function blocks
Master frequency ramp−function generator (DFRFG)
8.2
8.2.4
l
8.2−17
EDSVF9383V EN 7.1−04/2012
The profile generator can accept a phase difference between the set phase
and the actual phase of up to ±2140000000 inc (= 32000 revolutions).
ƒ A limit value can be set for the permissible phase difference via C0754.
ƒ If the limit value is reached, DFRFG1−FAIL is set to HIGH and the value is
saved.
ƒ DFRFG1−FAIL is only set to LOW with DFRFG1−RESET = HIGH.
Monitoring the phase
difference
Advertising