Configuration

Function blocks

Internal motor control with V/f characteristic control (MCTRL1)

8

8.2

8.2.6

l

8.2−33

EDSVF9383V EN 7.1−04/2012

After a signal request, the motor is decelerated to standstill when an internal
ramp function generator has been activated.

Mode of operation

ƒ Quick stop is active

– MCTRL−QSP = HIGH
– The control word DCTRL−QSP is applied
– DC injection braking (GSB) is not active (GSB has priority over quick

stop)

ƒ If quick stop is active, the motor brakes to standstill with the

deceleration time set in C0105. MCTRL−QSP−OUT is set to HIGH.

ƒ After a signal, the motor is braked by injecting a DC current.

ƒ Braking in generator mode must be used for controlled brake ramps.

ƒ The hold time (C0107) has no influence. The motor remains braked

until MCTRL−GSB is set to LOW.

)

Note!

Manual DC injection braking has priority over quick stop.

Setting

Selection

Code

Description

DC braking current

C0036

DC braking current with which the motor is braked

(

Stop!

An excessive DC braking current and braking time can thermally
overload the motor. Special care must be taken when using
self−ventilated motors.

Activation

The input MCTRL−GSB in the function block MCTRL is triggered with HIGH
level.

ƒ MCTRL−GSB = HIGH: Function is activated

ƒ MCTRL−GSB = LOW: Function is not activated

Quick stop (QSP)

Manual DC injection braking