Adjusting the motor

Automatic collection of motor data

6.6

6.6.6

l

6.6−17

EDSVF9383V EN 7.1−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0148

s

ident run

0

0

WRK
stop

Ready

Motor data identification
1. Inhibit controller, wait until

drive has stopped

2. Enter the correct values of the

motor nameplate into C0087,
C0088, C0089, C0090, C0091

3. Set C0148 = 1, confirm with

v

4. Enable controller

The identification
– starts,

c goes off. The

motor "whistles" but does
not rotate!

– lasts approx. 1 ... 2 min
– is completed when

c is lit

again

5. Inhibit controller:

^
6.6−15

1

WRK run Start identification

C0149

s

Auto ident

0

0

Id
inactive

Automatic identification is
inactive

Automatic motor data
identification
1. Inhibit controller, wait until

drive has stopped

2. Enter the correct values of the

motor nameplate into C0087,
C0088, C0089, C0090, C0091

3. Set C0149 = 1, confirm with

v

4. Enable controller

The identification
– starts,

c goes off. The

motor "whistles" but does
not rotate!

– lasts approx. 1 ... 2 min
– is completed when

c is lit

again

5. Inhibit controller:

^
6.6−15

1

Id active Automatic identification is

active

l

The identification starts
automatically after
controller enable

l

After a faulty
identification, the process
is restarted after TRIP
RESET or mains switching
and subsequent
controller enable