Lenze EVF9383 User Manual

Page 104

Advertising
background image

Control terminals
With function "Safe torque off" active

5.6
5.6.3

l

5.6−6

EDSVF9383V EN 7.1−04/2012

Supply via external voltage source

GND2

+24V

+5 V

DIGOUT4

E5

A2 A3 A4 ST1ST2 59

39

3k

47k

50mA

50mA

50mA

50mA

X5 28 E1 E2 E3 E4

3k

3k

3k

3k

3k

DC 24 V

(+18 V … +30 V)

X11 K31K32 33 34

S1

S2

IN1 IN2 IN3 IN4

+

K

SR

+

A1

Z1

X3

GND1

GND1

X6

1

2

3

4

7

7

62 63

242R

3.3nF

100k

100k

100k

100k

1
2
3
4
5
6

AIN1

AIN2

AOUTx

AOUT2

AOUT1

1

3

2

4

7

10k

10k

9300vec136

Fig. 5.6−4

Wiring of digital and analog inputs/outputs with active "Safe torque off" function
and external voltage source

S1

Deactivate pulse inhibit (1st disconnecting path)

S2

Enable controller (2nd disconnecting path)

Z1

Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function

X5/A4 Feedback via a digital output (e. g. DIGOUT4)

NO contact or NC contact

Z

Load
Minimum wiring required for operation

Terminal assignment in the Lenze setting:

^ 5.6−9

)

Note!

Supplying the digital inputs via an external voltage source
enables a backup operation in the case of mains failure. After
switching off the mains voltage, all actual values are continued
to be detected and processed.

ƒ

Connect the positive pole of the external voltage source with
X5/59 to establish the backup operation in the event of mains
failure.

ƒ

The external voltage source must be able to supply a current

³ 1 A.

ƒ

The starting current of the external voltage source is not
limited by the controller. Lenze recommends the use of
voltage sources with current limitation or with an internal
impedance of Z > 1

W.