Configuration – Lenze EVF9383 User Manual

Page 277

Advertising
background image

Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−61

EDSVF9383V EN 7.1−04/2012

Vector control

Use C0021 to change the influence of the rotor resistance (C0082)
proportionally:

ƒ Reduce the value in C0021 at an increasing speed (negative values)

ƒ Increase the value in C0021 at a decreasing speed

)

Note!

When setting the vector control mode, the slip compensation
(C0021) is automatically set to 0.0 %.

ƒ

When you switch back to the V/f characteristic control mode,
the slip compensation must be re−adapted.

If the motor may only rotate in one direction, you can limit the output
voltage generation to one direction of rotation via C0909.

Code

Description

C0909 = 1

The motor rotates in both directions

C0909 = 2

Motor rotates clockwise, "positive direction of rotation"
(View of the motor shaft)

C0909 = 3

Motor rotates counter−clockwise, "negative direction of rotation"
(View of the motor shaft)

Slip compensation

Inhibiting the direction of
rotation