Basic devices in the power range 110 ... 200 kW

Mains connection 400 V devices

5.4

5.4.2

l

5.4−3

EDSVF9383V EN 7.1−04/2012

5.4.2

Mains connection 400 V devices

(

Stop!

The user is responsible for sufficient strain relief!

BR2

BR1

PE

U

V

W

L1

L2

L3 PE

L1, L2,
L3

25-30 Nm

M8

221-264 lb-in

PE

15-20 Nm

M6

133-176 lb-in

40 mm

9300VEC003

Fig. 5.4−2

Mains connection example

BR1, BR2

Brake resistors can only be operated with variants V060 and
V110

5.4.3

Mains connection 400/500 V devices

(

Stop!

The user is responsible for sufficient strain relief!

BR2

BR1

+UG -UG

PE

U

V

W

L1

101

102

103

104

L2

L3

PE

L1, L2,
L3

25-30 Nm

M8

221-264 lb-in

PE

15-20 Nm

M6

133-176 lb-in

40 mm

9300VEC032

Fig. 5.4−3

Mains connection example

BR1, BR2

Brake resistors can only be operated with variants V270 and
V300