Adjusting the motor
Motor temperature monitoring with KTY

6.6
6.6.4

l

6.6−12

EDSVF9383V EN 7.1−04/2012

)

Note!

ƒ

In the Lenze setting, the motor temperature monitoring is
switched off!

ƒ

If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!

Use C0594 = 0 or C0594 = 2 to activate the motor temperature monitoring
via X8. In addition, the connection is monitored for short circuit and
interruption.

1. Connecting the monitoring circuit of the motor to X8/5 and X8/8.

2. Setting controller reaction to short circuit or interruption of the

connection:
– C0594 = 3: Monitoring is switched off.
– C0594 = 0: TRIP error message (display of keypad: Sd6

a)

– C0594 = 2: Warning signal (display of keypad: Sd6

e)

Monitoring with a fixed operating temperature (150 °C)

1. Set response of the controller:

– C0583 = 3: temperature monitoring of the motor switched off.
– C0583 = 0: TRIP error message (keypad display: OH3

a)

– C0583 = 2: warning signal (keypad display: OH3

e)

Monitoring with a variable operating temperature (45...150 °C)

1. Set the operating temperature in C0121.

2. Set response of the controller:

– C0584 = 3: temperature monitoring of the motor switched off.
– C0584 = 2: warning signal (keypad display: OH7

e)

Activation

Adjustment