4 connection of external brake resistor, Connection of external brake resistor, Braking operation – Lenze EVF9383 User Manual

Page 431

Advertising
background image

Braking operation

Lenze brake resistors

Connection of external brake resistor

12

12.2

12.2.4

l

12.2−3

EDSVF9383V EN 7.1−04/2012

12.2.4

Connection of external brake resistor

PES

BR1 BR2

Z1

PES

J

RB

RB

RB2

T1

RB1

T2

9300VEC033

Fig. 12.2−2

Brake resistor connection

RB1, RB2 Controller terminals for connecting the brake resistor
Z1

Brake resistor

PES

HF−shield end by PE connection through shield bracket.

ƒ Brake resistors can get hot and under certain conditions a brake

resistor can even burn down. For this reason, the brake resistors must
be mounted so that the possibly high temperatures cannot cause any
damage.

ƒ Provide a safety shutdown in the event the brake resistor overheats.

ƒ Use the thermal contacts of the brake resistor (e.g. T1 / T2) as control

contacts to disconnect the controller from the cable!

ƒ Only use shielded brake resistor cables.

ƒ Connect the shield close to the controller and close to the brake resistor

with a surface as large as possible to the mounting plate by using a
shield clamp.

ƒ The shield of the control cables for digital signals (temperature

monitoring T1 / T2) must be connected at both sides (controller and
brake resistor).

ƒ Unshielded cables between shield clamp and connection terminals

must not be longer than 40 mm.

Important notes