Configuration

Function blocks
Internal motor control with V/f characteristic control (MCTRL1)

8

8.2
8.2.6

l

8.2−26

EDSVF9383V EN 7.1−04/2012

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0006

s

Op mode

5

Selection of the operating mode
for the motor control

1

vector ctrl

Vector control
without or with
speed feedback

In case of the first selection enter
the motor data and identify them
with C0148.

^ 6.8−8

5

V / f

V/f characteristic
control

Commissioning without
identification of the motor data is
possible

l

Advantage of identification
with C0148: Improved smooth
running at low speeds

^ 6.8−4

C0010 N

min

0

0

{1 rpm}

36000

l

Reference value
for the absolute
and relative
setpoint selection
for the
acceleration and
deceleration
times

l

C0059 must be
set correctly

l

Set C0010 <
C0011

l

C0010 is only
effective in case
of analog setpoint
selection via AIN1

Important: For
parameter setting
via interface, major
changes in one step
should only be made
when the controller
is inhibited.

Minimum
speed

^
6.10−1

C0011 N

max

3000 0

{1 rpm}

36000

Maximum
speed

C0014 V/f charact.

0

Characteristic in the V/f
characteristic control mode

^
8.2−25

0

Linear

Linear V/f characteristic

1

square

Square V/f characteristic

C0015 Rated freq

50

10

{1 Hz}

5000 V/f−rated frequency

In C0015 you can set a base
frequency which differs from the
rated motor frequency (C0089)

l

Lenze setting: C0015 = C0089

l

Changing C0086 or C0089
overwrites the value in C0015

^
8.2−25

C0016 Umin boost

0.00

0.00

{0.01 %}

100.00 U

min

boost (FCODE)

l

C0016 = 1 % corresponds to a
boost of 1 % of the rated motor
voltage (C0090)

l

Code is freely configurable

^ 6.8−4