Configuration – Lenze EVF9383 User Manual

Page 243

Advertising
background image

Configuration

Function blocks

Internal motor control with V/f characteristic control (MCTRL1)

8

8.2

8.2.6

l

8.2−27

EDSVF9383V EN 7.1−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0018 fchop

6

Switching frequency of the
inverter

l

General rule: The lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity

factor

l

Observe derating indications
for high switching frequencies

l

The max. output frequency
(f

max

) is:

– fchop = 4 kHz

Þ

f

max

= 300 Hz

– fchop = 2 kHz

Þ

f

max

= 150 Hz

– fchop = 1 kHz

Þ

f

max

= 150 Hz

^ 6.9−1

1

1 kHz sin

loss−optimised

2

2 kHz sin

concentricity−opti
mised

3

4 kHz f_top

power−optimised

4

4 kHz sin

noise−optimised

6

4/2 kHz sin

noise/concentricit
y−optimised with
automatic
change−over to
low switching
frequency

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−40

C0022 Imax current

à

0

{0.1 A}

− I

max

limit in motor mode

à

depending on C0086

^
6.6−14

C0023 Imax gen.

à

0

{0.1 A}

− I

max

limit in generator mode

à

depending on C0086

^
6.6−14

C0036 DC brk value

0.0

0.0

{0.1 A}

− Set DC braking current

à

depends on the controller

^
8.2−25

^
8.2−40

C0042 DIS: QSP

Quick stop

l

Display only

^
8.2−25

^
8.2−40

0

QSP inactive

Quick stop is not active

1

QSP active

Quick stop is active

C0050 MCTRL−NSET2

−100.00

{0.01 %}

100.00 Speed setpoint, function block

MCTRL

l

Display of the speed in [%] of
C0011

^
8.2−25

^
8.2−40

C0051 MCTRL−NACT

−36000

{1 rpm}

36000 Actual speed value, function block

MCTRL

l

Read only

^
8.2−25

^
8.2−40

C0052 MCTRL−Umot

0

{1 V}

800 Motor voltage, function block

MCTRL

l

Read only

l

MCTRL−VACT = 100 % = C0090

^
8.2−25

^
8.2−40

C0053 UG−VOLTAGE

0

{1 V}

900 DC−bus voltage, function block

MCTRL

l

Read only

l

MCTRL−DCVOLT = 100 % =
1000 V

^
8.2−25

^
8.2−40

C0054 Imot

0.0

{0.1 A}

5000.0 Actual motor current, function

block MCTRL

l

Read only

l

MCTRL−IACT = 100 % = C0022

^
8.2−25

^
8.2−40

Advertising
This manual is related to the following products: