Configuration

Code table

8

8.5

l

8.5−38

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0640 Delay T

20.00 0.01

{0.01 s}

50.00 Time constant, function block

PT1−1

l

Time period by which the
output of analog signal is
delayed

See System
Manual
(extension)

C0641

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block PT1−1

C0642 DIS: IN

−199.99

{0.01 %}

199.99 Function block PT1−1

l

Display of the signal linked in
C0641

C0643 Delay T

20.00 0.01

{0.01 s}

50.00 Time constant, function block

PT1−2

l

Time period by which the
output of analog signal is
delayed

C0644

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block PT1−2

C0645 DIS: IN

−199.99

{0.01 %}

199.99 Function block PT1−2

l

Display of the signal linked in
C0644

C0650 DT1−1 gain

1.00

−320.00

{0.01 }

320.00 Gain, function block DT1−1

l

Gain of the analog input signal

See System
Manual
(extension)

C0651 Delay T

1.000 0.005

{0.01 s}

5.000 Time constant, function block

DT1−1

l

Time period by which the
output of analog signal is
delayed

C0652

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block DT1−1

C0653 Sensibility

1

1

15 bits

Input sensitivity, function block
DT1−1

l

According to the setting only
the indicated higher−order bits
are evaluated

2

14 bits

3

13 bits

4

12 bits

5

11 bits

6

10 bits

7

9 bits

C0654 DIS: IN

−199.99

{0.01 %}

199.99 Function block DT1−1

l

Display of the signal linked in
C0652

C0655 Numerator

1

−32767

{1}

32767 Configuration of conversion factor

with numerator and denominator,
function block CONV5

See System
Manual
(extension)

C0656 Denominator

1

1

{1}

32767

OUT [rpm]

+ IN [%] @

15000 rpm

100 %

@ C0655

C0656

C0657

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block CONV5

C0658 DIS: IN

−199.99

{0.01 %}

199.99 Function block CONV5

l

Display of the signal linked in
C0657

C0661

s

CFG: IN

1000 FIXED0%

^ Selection list 1

Configuration of analog input
signal, function block ABS1

l

Converts bipolar signals into
unipolar signals

See System
Manual
(extension)

C0662 DIS: IN

−199.99

{0.01 %}

199.99 Function block ABS1

l

Display of the signal linked in
C0661

Advertising