Configuration, Code table – Lenze EVF9383 User Manual

Page 301

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−13

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0130 DIS: act Ti

Active T

i

times for the speed

setpoint conditioning, function
block NSET

l

Display of the additional
acceleration and deceleration
times for the main setpoint
(C0101, C0103)

l

Activation via binary coding of
C0788/1 ... C0788/4

See System
Manual
(extension)

0

C12/C13

1

Tir1/Tif1

2

Tir2/Tif2

...

...

14

Tir14/Tif14

15

Tir15/Tif15

C0132

s

RFG fly delay

May only be changed by Lenze
service personnel!

C0133

s

HLG fly delay

May only be changed by Lenze
service personnel!

C0134 RFG charac

0

0

Linear

linear
characteristic

Ramp function generator
characteristic, function block NSET

l

Characteristic of the main
setpoint

See System
Manual
(extension)

1

S−shaped

S−shaped
characteristic

C0135 Control word

0

Bit

Assignment

Control word, function block AIF

l

Decimal control word when
networked via automation
interface AIF

l

16−bit information, binary
coded

See System
Manual
(extension)

0

reserved

1

reserved

2

reserved

3

Quick stop

4

reserved

5

reserved

6

reserved

7

reserved

8

Operation inhibited

9

Controller inhibit

10

TRIP SET

11

Trip reset

12

reserved

13

reserved

14

reserved

15

reserved

C0136

Display of the control words in
C0135, AIF−IN and CAN−IN1

See System
Manual
(extension)

1 Ctrl wrd C135

Control word C0135

2 Ctrl wrd CAN

Control word CAN

3 Ctrl wrd AIF

Control word AIF

C0141 FCODE (setval)

0.00

−199.9

{0.01 }

199.99 Main setpoint, freely configurable

code (FCODE)

l

Used as main setpoint in the
basic configurations
C0005 = xxx1

C0142 Start options

May only be changed by Lenze
service personnel!

C0143 limit 2 kHz

0.0

0.0

{0.1 Hz}

20.0 Speed−dependent switching

threshold

l

Threshold for automatic
switching frequency reduction

l

The controller changes
automatically to 2 kHz when
this value falls below the
threshold

^
8.2−25

^
8.2−40

Advertising
This manual is related to the following products: