Configuration

Function blocks

Master frequency input (DFIN)

8

8.2

8.2.2

l

8.2−7

EDSVF9383V EN 7.1−04/2012

In C0425 the output signal can be adapted:

ƒ To the encoder at X9 or

ƒ To the upstream controller with master frequency cascade/master

frequency bus.

Transfer function

Calculating the output signal:

DFIN−OUT [rpm]

+ f [Hz] @ 60

C0425

Example:

The input frequency amounts to 200 kHz, the number of increments
corresponds to 2048 inc/rev. (C0425 = 3).

DFIN−OUT [rpm]

+ 200000 Hz @ 60

2048 +

5859 rpm

Signal adaptation

Signal adaptations other than by squaring in C0425 can be achieved by
connecting a function block.

Example:

The function block CONV3 shall convert the speed signal into a quasi analog
signal.

Calculating the output signal at CONV3:

CONV3−OUT [%]

+ f [Hz] @ 0.4

C0425

@ C0950

C0951

Interconnecting function blocks:

CONV3

CONV3-OUT

CONV3-IN

C0953

C0952

C0950

C0951

C0425

C0427

DFIN

DFIN-OUT

C0426

X9

fb_dfin_01

Fig. 8.2−6

Digital frequency input (DFIN) with connected converter

)

Note!

If a master frequency is output to DFOUT−AN−IN or DFOUT−DF
(C0540 = 0 or C0540 = 1) and an incremental encoder is
evaluated via X8, the function block DFIN cannot be used
anymore.
If the input signals at X8 or X9 are output to X10, (C0540 = 4 or
C0540 = 5), this restriction does not exist.

Adjusting the output signal