Basics for wiring according to EMC

Shielding

5.3

5.3.1

l

5.3−1

EDSVF9383V EN 7.1−04/2012

5.3

Basics for wiring according to EMC

5.3.1

Shielding

The shielding quality is determined by a good shield connection:

ƒ Connect the shield with a surface as large as possible.

ƒ Use a conductive clamp to connect the shield to the conductive and

grounded mounting plate with a surface as large as possible.

ƒ Unshielded cable ends must always be as short as possible.

5.3.2

Mains connection, DC supply

ƒ You can use unshielded single cores or unshielded cables to connect

the controller and the mains choke to the mains.

ƒ For DC−bus operation or DC supply, use shielded cables.

ƒ The cable cross−section must be dimensioned for the assigned fuse

protection (national and regional regulations).