6 fuses and cable cross-sections, Fuses and cable cross−sections – Lenze EVF9383 User Manual

Page 78

Advertising
background image

Basic devices in the power range 110 ... 200 kW
Fuses and cable cross−sections

5.4
5.4.6

l

5.4−6

EDSVF9383V EN 7.1−04/2012

5.4.6

Fuses and cable cross−sections

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 40 °C, no bundling of the cables or
cores, three loaded cores. The data are recommendations. Other
dimensionings/laying systems are possible (e.g. in accordance with VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current
device (RCD) or a fault current monitoring unit (RCM) is used for protection in
the case of direct or indirect contact, only one RCD/RCM of the following type
can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for

connection to a 1−phase system

Alternatively another protective measure can be used, like for instance
isolation from the environment by means of double or reinforced insulation,
or isolation from the supply system by using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply
and controller.

Observe all national and regional regulations!

9300

Fuse

Cable cross−section

FI

1)

Rated fuse current

Laying system F

L1, L2, L3

PE

Type

[A]

[mm

2

]

[mm

2

]

[mA]

EVF9335−EVV
EVF9335−EVVxxx

250

150

2 × 50

1)

95

300

EVF9336−EVV
EVF9336−EVxxx

315

150

2 × 50

1)

95

300

EVF9337−EVV
EVF9337−EVVxxx

315

150

2 × 50

1)

95

300

EVF9338−EVV
EVF9338−EVVxxx

400

240

2 × 95

1)

150

300

1)

Two conductors per path; both conductors must have the same cross−section

2)

Universal current−sensitive earth−leakage circuit breaker

9300

Fuse

Cable cross−section

Quantity

Rated fuse current

Laying system F

+U

G

, −U

G

PE

Type

[A]

[mm

2

]

[mm

2

]

EVF9335−EVV2xx
EVF9335−EVV300

1

400

2 × 50

1)

95

EVF9336−EVV2xx
EVF9336−EVV300

1

400

2 × 50

1)

95

EVF9337−EVV2xx
EVF9337−EVV300

2

350

2 × 95

1)

95

EVF9338−EVV2xx
EVF9338−EVV300

2

400

2 × 95

1)

150

1)

Two conductors per path; both conductors must have the same cross−section

Installation in accordance
with EN 60204−1

Fuses and cable cross−sections
for the mains connection

Fuses and cable cross−sections
for DC−bus connection