6 rated data (devices for 400/500v mains), 1 rated data for 400 v mains voltage, Rated data (devices for 400/500v mains) – Lenze EVF9383 User Manual

Page 43: Rated data for 400 v mains voltage, Technical data

Advertising
background image

Technical data

Rated data (devices for 400/500V mains)

Rated data for 400 V mains voltage

3

3.6

3.6.1

l

3.6−1

EDSVF9383V EN 4.0−11/2007

3.6

Rated data (devices for 400/500V mains)

)

Note!

Types EVF9335 ... EVF9383 for 400 V/500 V mains voltage are
suitable for DC supply or DC−bus operation together with
controllers of the 9300 series.

3.6.1

Rated data for 400 V mains voltage

Basis of the data

Voltage

Frequency

Supply

3/PE AC 400 V

[U

N

]

340 V − 0 % ... 577 V + 0 %

45 Hz − 0 % ... 65 Hz + 0 %

DC 565 V (alternatively)

[U

DC

]

DC 480 V − 0 % ... 800 V + 0 %

˘

Output voltage

[U

OUT

]

3 ~ 0 ... U

N

0 ... 300 Hz

9300

Mains current

1)

Typical motor power

ASM (4−pole)

Power loss

Type

I

r

[A]

P

N

[kW]

P

N

[hp]

P

V

[kW]

EVF9335−EVVxxx

2)

200

110

150

2.8

EVF9336−EVVxxx

2)

238

132

200

3.3

EVF9337−EVVxxx

2)

285

160

250

4.0

EVF9338−EVVxxx

2)

356

200

300

5.0

EVF9381−EVVxxx

2)

475

250

350

6.6

EVF9382−EVVxxx

2)

570

315

450

8.0

EVF9384−EVVxxx

2)

713

400

550

10.0

The currents for EVF9381 ... EVF9383 are to be considered as total currents of master and slave

1)

For a controller switching frequency of 2 kHz

2)

Device in variant V210, V240, V270 or V300

9300

Output currents

Rated current

Maximum current

2)

1 kHz

1)

2 kHz

1)

4 kHz

1)

1 kHz

1)

2 kHz

1)

4 kHz

1)

Type

I

N1

[A]

I

N2

[A]

I

N4

[A]

I

M1

[A]

I

M2

[A]

I

M4

[A]

EVF9335−EVVxxx

3)

210

210

210

315

315

315

EVF9336−EVVxxx

3)

250

250

250

375

375

375

EVF9337−EVVxxx

3)

300

300

270

450

450

405

EVF9338−EVVxxx

3)

375

375

330

560

560

495

EVF9381−EVVxxx

3)

500

500

500

750

750

750

EVF9382−EVVxxx

3)

600

600

540

900

900

810

EVF9384−EVVxxx

3)

750

750

660

1125

1125

990

The currents for EVF9381 ... EVF9383 are to be considered as total currents of master and slave
Bold print = Lenze setting

1)

Switching frequency of the inverter

2)

The currents apply to a periodic load change with an overcurrent time of 1 minute at a maximum
and a base load time of 2 minutes with maximally 75 % I

Nx

3)

Device in variant V210, V240, V270 or V300

Advertising
This manual is related to the following products: