6 adjusting the motor, 1 entry of motor data entry of motor data, Adjusting the motor – Lenze EVF9383 User Manual

Page 141: Entry of motor data

Advertising
background image

Adjusting the motor

Entry of motor data

6.6

6.6.1

l

6.6−1

EDSVF9383V EN 7.1−04/2012

6.6

Adjusting the motor

6.6.1

Entry of motor data

The vector control mode requires considerably more motor data than the V/f
characteristic control mode.

Basically all motor data should be entered independent of the operating
mode. This enables the controller to detect further data as e.g. slip
compensation (C0021), maximum torque (C0057), number of motor pole
pairs (C0059) always conclusively and enter them into the corresponding
codes.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0081

s

Mot power

à

0.01

{0.01 kW}

500.00 Rated motor power

à

Change of C0086 resets value
to factory setting

l

Change of C0081 sets C0086 =
0

C0086

s

Mot type

à

^ Motor selection list

Motor type selection

à

depending on the controller
used

l

Motor selection in C0086 sets
the corresponding parameters
in C0021, C0022, C0081,
C0087, C0088, C0089, C0090,
C0091

^
6.6−1

C0087

s

Mot speed

à

50

{1 rpm}

36000 Rated motor speed

à

depending on C0086

l

Motor selection in C0086 set
the corresponding rated motor
speed in C0087

l

Change of C0087 sets
C0086 = 0

^
6.6−1

C0088

s

Mot current

à

0.5

{0.1 A}

1000.0 Rated motor current

à

depending on C0086

l

Motor selection in C0086 sets
the corresponding rated motor
current in C0088

l

Change of C0088 sets C0086 =
0

^
6.6−1

C0089

s

Mot frequency

à

10

{1 Hz}

5000 Rated motor frequency

à

depending on C0086

l

Motor selection in C0086 sets
the corresponding rated motor
frequency in C0089

l

Change of C0089 sets
C0086 = 0

^
6.6−1

Description

Advertising