Configuration, Code table – Lenze EVF9383 User Manual

Page 299

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−11

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0101

0.00

{0.01 s}

999.90 Additional acceleration times for

speed setpoint conditioning,
function block NSET

l

Additional acceleration and
deceleration times for the main
setpoint

l

Activation via binary coding of
digital input signals in
C0788/1 ... C0788/4

l

For coding see description of
function block NSET

See System
Manual
(extension)

1 add Tir

0.00

2 add Tir

0.00

... ...

...

15 add Tir

0.00

C0103

0.00

{0.01 s}

999.90 Additional deceleration times for

speed setpoint conditioning,
function block NSET

l

Additional acceleration and
deceleration times for the main
setpoint

l

Activation via binary coding of
digital input signals in
C0788/1 ... C0788/4

l

For coding see description of
function block NSET

1 add Tif

0.00

2 add Tif

0.00

... ...

...

15 add Tif

0.00

C0104

s

select accel.

0

Selection of acceleration function
of the linear ramp function
generator of NSET

See System
Manual
(extension)

0

a = const

Constant acceleration

1

t = const

Constant time

2

s = const

Constant path

C0105 QSP Tif

5.00

0.00

{0.01 s}

999.90 Quick stop deceleration time

l

The deceleration time refers to
a speed variation of C0011 ... 0

^
8.2−25

^
8.2−40

C0107 holding time

0.00

0.00

{0.01 s}

9999.90 Hold time for automatic DC

injection braking (Auto−GSB)

^
8.2−25

^
8.2−40

C0108

−199.99

{0.01 %}

199.99 Free control code FCODE108/1

and FCODE108/2

^ 6.5−6

See System
Manual
(extension)

1 FCODE (gain)

100.0

0

Gain of analog output signal
AOUT1 (X6/62)

l

100 % = gain 1

2 FCODE (gain)

100.0

0

Gain of analog output signal
AOUT2 (X6/63)

l

100 % = gain 1

C0109

−199.99

{0.01 %}

199.99 Free control code FCODE109/1

and FCODE109/2

1 FCODE (offset)

0.00

Offset of analog output signal
AOUT1 (X6/62)

2 FCODE (offset)

0.00

Offset of analog output signal
AOUT2 (X6/63)

C0114

0

High active

HIGH level is
active

Inversion of digital input signals at
X5, function block DIGIN

^ 6.5−1

See System
Manual
(extension)

1

LOW active

LOW level is active

1 DIGIN1 pol

0

Terminal X5/E1

2 DIGIN2 pol

0

Terminal X5/E2

3 DIGIN3 pol

0

Terminal X5/E3

4 DIGIN4 pol

1

Terminal X5/E4

5 DIGIN5 pol

0

Terminal X5/E5

5 DIGIN6 (ST) pol

0

Terminal X5/ST

Advertising