Troubleshooting and fault elimination

Fault elimination

Behaviour in case of overvoltage in the DC bus (OU message)

9

9.4

9.4.3

l

9.4−3

EDSVF9383V EN 7.1−04/2012

9.4.3

Behaviour in case of overvoltage in the DC bus (OU message)

If the DC−bus voltage (U

DC

) exceeds the switch−off threshold OU, pulse

inhibit will be set. At the same time, an internal timer for a delay time
(C0912) will be started.

Pulse inhibit will be reset, if the voltage falls below the switch−on threshold
OU and the delay time has elapsed.

Types EVF93xx−EVV210, EVF93xx−EVV240, EVF93xx−EVV270 and EVF93xx−EVV300

Mains voltage range

C0173

Switch−off threshold

OU

Switch−on threshold

OU

< 400 V

Operation with or
without brake
transistor

0

770 V

755 V

400 V

Operation with or
without brake
transistor

1

*

770 V

755 V

460 V

Operation with or
without brake
transistor

2

770 V

755 V

480 V

Brake transistor

3

770 V

755 V

480 V

Brake transistor

4

800 V

785 V

500 V

Operation with or
without brake
transistor

5

900 V

885 V

*

Lenze setting

Types EVF93xx−EV, EVF93xx−EVV060 and EVF93xx−EVV110

Mains voltage range

C0173

Switch−off threshold

OU

Switch−on threshold

OU

400 V

Operation with or
without brake
transistor

Read only

700 V

685 V

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0912 OV delay time

à

{1 ms}

− Delay time of the pulse enable

after an OU message

à

Depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor

l

The time is derived from the
double rotor time constant

^
8.2−25

^
8.2−40

^
9.4−3

Description

Thresholds for DC−bus
overvoltage (OU)

Advertising