Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−49

EDSVF9383V EN 7.1−04/2012

Temperature detection

For motors with temperature detection (KTY83−110) the controller can
consider temperature changes in its motor model. The accuracy and stability
of the vector control are improved considerably.

ƒ Sensor connection:

– X8/5 = −KTY (rt/ws/bl)
– X8/8 = +KTY (br/gr/sw)

)

Note!

You can also use the thermal sensor (KTY) without speed
feedback.

ƒ When monitoring SD6 (C0594) is activated, temperature feedback is

activated at the same time.

ƒ First, activate the temperature feedback and then start the motor

identification to consider the motor temperature.

ƒ In addition, you can activate and parameterise the monitoring

functions OH3 (C0583) and OH7 (C0584).

ƒ The current motor temperature can be displayed via C0063.

Setting integral action component

To initialise the speed controller with a starting torque, the integral action
component of the speed controller can be described via MCTRL−I−SET
(starting value) and MCTRL−I−LOAD (control signal).

Input signal

Effect

MCTRL−I−LOAD = HIGH

l

The speed controller transmits the value at MCTRL−I−SET to its
integral action component

l

The P component is switched off

MCTRL−I−LOAD = LOW

The speed controller is active