background image

Basic devices in the power range 110 ... 200 kW
DC supply 400/500 V devices

5.4
5.4.4

l

5.4−4

EDSVF9383V EN 7.1−04/2012

5.4.4

DC supply 400/500 V devices

(

Stop!

The user is responsible for sufficient strain relief!

ƒ For compliance with EMC requirements, Lenze recommends to use

shielded DC−bus cables.

ƒ Shield clamps are not included in the scope of supply.

BR2

BR1

+UG -UG

PE

U

V

W

L1

101

102

103

104

L2

L3

PE

40 mm

PE

15-20 Nm

M6

133-176 lb-in

+U

G

-U

G

25-30 Nm

M8

221-264 lb-in

max.

300 mm

1

0

9300VEC074

Fig. 5.4−4

Connection example to +U

G

and −U

G

BR1, BR2

Brake resistors can only be operated with variants V270 and V300

0

Connect the DC−bus cable shield to the conductive control cabinet
mounting plate with a contact surface as large as possible by using
the shield clamps.

1

Conductive surface

Ensure to have the poles right!

5.4.5

Fan connection 400/500 V devices

Lay a bridge between the terminals when a controller is operated on a mains.

AC 340 ... 440 V

AC 440 ... 577 V

(when being delivered)

L1

L2

101

102

103

104

101

102

103

104

L1

L2

9300vec044

9300vec045

Fan connection when
controller is supplied with
mains voltage