4 overview of monitoring functions, Overview of monitoring functions, Configuration – Lenze EVF9383 User Manual

Page 287

Advertising
background image

Configuration

Overview of monitoring functions

8

8.4

l

8.4−1

EDSVF9383V

EN 7.1−04/2012

8.4

Overview of monitoring functions

The responses of monitoring functions can be partly parameterised via codes ˘ in GDC in the parameter menu under
Monitoring ˘.

Monitoring

Possible responses

l Lenze setting

ü Setting possible

Error message

Description

Source

CoDe

TRIP

Message

Warning

Off

0071

CCr

System fault

Internal

l

x091

EEr

External monitoring (activated via DCTRL)

FWM

C0581

l

ь

ь

ь

Voltage supply

2020

OU

Overvoltage in the DC bus (C0173)

MCTRL

l

1030

LU

Undervoltage in the DC bus (C0173)

MCTRL

l

0107

H07

Internal fault (power section)

Internal

l

Communication

x061

CE0

Communication error on the automation interface (AIF)

AIF

C0126

ь

ь

l

x062

CE1

Communication error at process data input object CAN1_IN (monitoring time can be set
with C0357/1)

CAN1_IN

C0591

ь

ь

l

x063

CE2

Communication error at process data input object CAN2_IN (monitoring time can be set
with C0357/2)

CAN2_IN

C0592

ь

ь

l

x064

CE3

Communication error at process data input object CAN3_IN (monitoring time can be set
with C0357/3)

CAN3_IN

C0593

ь

ь

l

x065

CE4

BUS−OFF state of the system bus (CAN)
(too many faulty telegrams)

CAN

C0595

ь

ь

l

Temperatures / sensors

0050

OH

Heatsink temperature > 85° C

MCTRL

l

x053

OH3

Motor temperature > 150° C

MCTRL

C0583

ь

ь

l

x054

OH4

Heatsink temperature > C0122

MCTRL

C0582

l

ü

x057

OH7

Motor temperature > C0121

MCTRL

C0584

l

ü

x058

OH8

Motor temperature across inputs T1 and T2 is too high.
Please note: In the case of "Warning" (C0585 = 2) or "Off" (C0585 = 3), the drive can be
destroyed if the fault is not eliminated in time!

MCTRL

C0585

ь

ь

l

x086

Sd6

Thermal sensor error at motor (X7 or X8)

MCTRL

C0594

ь

ь

l

x110

H10

Thermal sensor error at heatsink

FWM

C0588

l

1)

1)

x111

H11

Thermal sensor error in the device interior

FWM

C0588

l

1)

1)

Motor / feedback system

0011

OC1

Motor cable overcurrent

MCTRL

l

0012

OC2

Motor cable earth fault

MCTRL

l

0013

OC3

Overload at acceleration or deceleration

MCTRL

l

Advertising
This manual is related to the following products: