Switching frequency of the inverter

6.9

l

6.9−2

EDSVF9383V EN 7.1−04/2012

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0018 fchop

6

Switching frequency of the
inverter

l

General rule: The lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity

factor

l

Observe derating indications
for high switching frequencies

l

The max. output frequency
(f

max

) is:

– fchop = 4 kHz

Þ

f

max

= 300 Hz

– fchop = 2 kHz

Þ

f

max

= 150 Hz

– fchop = 1 kHz

Þ

f

max

= 150 Hz

^
6.9−1

1

1 kHz sin

loss−optimised

2

2 kHz sin

concentricity−opti
mised

3

4 kHz f_top

power−optimised

4

4 kHz sin

noise−optimised

6

4/2 kHz sin

noise/concentricit
y−optimised with
automatic
change−over to
low switching
frequency

C0144

s

OH switch

1

0

Switch off

Switch−over is not
active

Temperature−dependent
switching frequency reduction

l

If the heatsink temperature set
in C0122 is reached (warning

OH4), the controller switches
to 2 kHz

1

Switch on

Switch−over is
active

C0144 = 0 (no temperature−dependent switching frequency reduction)

If the maximum permissible heatsink temperature (

J

max

) is exceeded when

operating with automatic switching frequency reduction, the inverter is
inhibited, TRIP "OH" (overtemperature) is set and the motor coasts without
torque.

C0144 = 1 (temperature−dependent switching frequency reduction is
active):

ƒ If the heatsink temperature set in C0122 (overtemperature OH4) is

reached when operating with automatic switching frequency
reduction, the controller automatically reduces the switching
frequency to 2 kHz, thus keeping the operation running.

ƒ After the heatsink has cooled down, the controller automatically

switches to the set switching frequency again.

Function of automatic
switching frequency
reduction