8 motor connection, Motor connection, Stop – Lenze EVF9383 User Manual

Page 93

Advertising
background image

Basic devices in the power range 250 ... 400 kW

Motor connection

5.5

5.5.8

l

5.5−11

EDSVF9383V EN 7.1−04/2012

5.5.8

Motor connection

ƒ To comply with the EMC regulations, Lenze recommends to use

shielded motor cables.

ƒ Shield clamps are not included in the scope of supply.

(

Stop!

The user is responsible for sufficient strain relief!

In order to connect the motor cables of master and slave to the motor, the
outputs must be connected in parallel.

It is important for the parallel connection of the inverter outputs that the
outputs are decoupled by means of an inductance between master and
slave. The length of the motor cables determine whether the inductance of
the cables is sufficient for a decoupling.

2 motor connections ensure sufficient decoupling.

ƒ Decoupling via motor chokes

If the single motor cable length is

£ 10 m, master and slave must be

connected in parallel via chokes on the motor side to achieve a sufficient
decoupling between master and slave.

ƒ Decoupling via motor cables

If the single motor cable length is > 10 m, the motor cables of master and
slave can be connected in parallel at the motor to achieve a sufficient
decoupling between master and slave.

Decoupling via motor chokes

Decoupling via motor cables

M

3~

PE

PE

U

U

V

V

W

W

Z1

Z2

PE

£

10
m

PE

PE

PE

PE U

V W

M

3~

PE U

V W

PE

PE

PE

>10

m

9300VEC026

9300VEC008

Fig. 5.5−11

Variants for parallel connection of master and slave (motor side)

Z1, Z2

Motor choke

for controller

ELM3−0003H275

EVF9381

ELM3−0002H320

EVF9382

ELM3−0002H410

EVF9383

Parallel connection of master
and slave (motor side)