Lenze EVF9383 User Manual

Page 143

Advertising
background image

Adjusting the motor

Entry of motor data

6.6

6.6.1

l

6.6−3

EDSVF9383V EN 7.1−04/2012

By selecting the motor in C0086 all required motor data are automatically
entered into the following codes.

Code

Description

Code

Description

C0022

Limit current for operation in motor mode C0087

Rated motor speed

C0023

Limit current for operation in generator
mode

C0088

Rated motor current

C0081

Rated motor power

C0089

Rated motor frequency

C0082

Motor rotor resistance

C0090

Rated motor voltage

C0084

Motor stator resistance

C0091

Power factor cos

j

C0085

Motor leakage inductance

C0092

Motor stator inductance

1. Select a similar motor in C0086.

– Selection criteria: Connection method, rated motor power, rated

motor frequency

2. Enter the motor data of the motor nameplate or data sheet into C0081,

C0087, C0088, C0089, C0090 and C0091.

By changing from star to delta connection and changing the base frequency
(f

base

= 87 Hz), the induction machine (f

N

= 50 Hz) develops

Ǡ

three times the

power with a frequency of 87 Hz. In the total range the machine runs with
a

Ǡ

3 times higher delta current, which must be provided by the controller.

Example

A motor with the following data is to be connected in delta connection:

ƒ DSM 50 Hz;

D/Y 230/400 V; 18.5 kW; 62/35 A, 1450 min

−1

, cos

j = 0.88

Sequence

Note

1.

Enter C0086 = 263
(DXRAXX 180−12−87; 32.4 kW;
87 Hz)

Select a motor in C0086, which has a

Ǡ

3 times

higher rated motor power with delta connection.

2.

Enter C0087 = 2548 min

−1

Consider the slip speed. With a rated motor torque
the slip speed of an asynchronous motor is nearly
constant over the total speed range.
Calculation of the rated motor speed:

C0087

+ ( 3

Ǹ

* 1) @ n

0

) n

N

C0087

+ ( 3

Ǹ

* 1) @ 1500 min

*1

) 1450 min

*1

n

0

= synchronous speed

n

N

= rated motor speed at 50 Hz

3.

Enter C0088 = 62 A

Rated motor current for delta connection

4.

Enter C0090 = 400 V

Rated motor voltage for star connection

5.

Enter C0089 = 87 Hz

Rated motor frequency

6.

Enter C0091 = 0.88

Power factor cos

j

Lenze motor which is included
in C0086

Motor of another
manufacturer or a Lenze
motor which is not included in
C0086

Operating mode "87 Hz delta