Configuration, Code table – Lenze EVF9383 User Manual

Page 313

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−25

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0368 Sync Tx ID

128

1

{1}

256 Transmission identifier (Tx)

l

Identifier for generating a sync
telegram

C0369 Sync Tx Time

0

0

{1}

65000 Sync transmission time (Tx)

l

Transmission interval for the
object set in C0368

C0400 DIS: OUT

−199.99

{0.01 %}

199.99 Analog output signal, function

block AIN1

l

Read only

See System
Manual
(extension)

C0402

s

CFG: OFFSET

19502 FCODE−26/1

^ Selection list 1

Configuration offset, function
block AIN1

l

The offset is added to the input
signal at AIN1−IN

C0403

s

CFG: GAIN

19504 FCODE−27/1

^ Selection list 1

Configuration of gain, function
block AIN1

l

The gain is multiplied by the
input signal at AIN1−IN

C0404

−199.99

{0.01 %}

199.99 Function block AIN1

l

Display of the signals linked in
C0402 and C0404

1 DIS: OFFSET
2 DIS: GAIN

C0405 DIS: OUT

−199.99

{0.01 %}

199.99 Analog output signal, function

block AIN2

l

Read only

See System
Manual
(extension)

C0407

s

CFG: OFFSET

19503 FCODE−26/2

^ Selection list 1

Configuration of offset, function
block AIN2

l

The offset is added to the input
signal at AIN2−IN

C0408

s

CFG: GAIN

19505 FCODE−27/2

^ Selection list 1

Configuration of gain, function
block AIN2

l

The gain is multiplied by the
input signal at AIN2−IN

C0409

−199.99

{0.01 %}

199.99 Function block AIN2

l

Display of the signals linked in
C0407 and C0408

1 DIS: OFFSET
2 DIS: GAIN

C0420

s

Encoder const

512

1

{1 inc/rev}

8192 Number of increments for

incremental encoder at X8 or X9

l

Connect incremental encoders
with HTL−level on X9 only

^ 6.7−1

C0421

s

Enc voltage

5.00

5.00

{0.1 V}

8.00 Supply voltage for the incremental

encoder at X8
CAUTION! A wrong entry can
destroy the incremental encoder!

Advertising