Optimising the operating behaviour

Slip compensation

6.11

6.11.1

l

6.11−1

EDSVF9383V EN 7.1−04/2012

6.11

Optimising the operating behaviour

6.11.1

Slip compensation

The speed of an asynchronous machine decreases when being loaded. This
load−dependent speed drop is called slip. By setting C0021 the slip can be
partly compensated.

In the V/f characteristic control mode the slip compensation is only active at
operation without feedback (C0025 = 1).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−40

C0078 Tn slip CTRL

100

1

{1 ms}

6000 Integral−action time of slip

controller

l

Filter time for slip
compensation (C0021)

l

Only active with V/f
characteristic control

^
8.2−25