Operating mode
V/f characteristic control

6.8
6.8.1

l

6.8−6

EDSVF9383V EN 7.1−04/2012

Load−independent boost of the motor voltage for output frequencies below
the V/f rated frequency. This serves to optimise the torque behaviour.

C0016 must be adapted to the asynchronous motor used. Otherwise the
motor may be destroyed by overtemperature or the controller may be
operated with overcurrent:

1. Operate the motor in idle state at 5 ... 10 % of the rated speed (n

N

):

2. Increase V

min

until you reach the following motor current:

A Motor in short−time operation up to 0.5

 n

N

:

– For self−ventilated motors: I

motor

»

I

N motor

– For forced ventilated motors: I

motor

»

I

N motor

B Motor in continuous operation up to 0.5

 n

N

:

– For self−ventilated motors: I

motor

» 0.8  I

N motor

– For forced ventilated motors: I

motor

» I

N motor

)

Note!

Observe for all adjusting processes the thermal behaviour of the
connected asynchronous motor at low speeds:

ƒ

Usually, standard asynchronous motors with insulation class B
can be driven for a short time with its rated current in the
speed range up to 0.5

 n

N

.

ƒ

Contact the motor manufacturer for getting the exact setting
values for the max. permissible motor current of
self−ventilated motors in the lower speed range.

0

1

0

C0089

C0090

100 %

N

n
n

U

min

U

out

0

1

0

C0089

C0090

100 %

N

n
n

U

min

U

out

9300vec085

9300vec086

Fig. 6.8−4

Umin boost at linear and square−law V/f characteristic

Set U

min

boost

Advertising