Changing the assignment of the control terminals X5 and X6

Free configuration of digital outputs

6.5

6.5.2

l

6.5−3

EDSVF9383V EN 7.1−04/2012

6.5.2

Free configuration of digital outputs

ƒ The digital outputs X5/A1 ... X5/A4 can be freely linked with internal

digital signals.

ƒ One signal source can be linked with several targets.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0117

s

^ Selection list 2

Configuration of digital inputs
signals, function block DIGOUT
A change of the basic
configuration in C0005 changes
the signal assignment!

^
6.5−3

See System
Manual
(extension)

1 CFG: DIGOUT1

15000 DCTRL−TRIP

Terminal X5/A1

2 CFG: DIGOUT2

10650 CMP1−OUT

Terminal X5/A2

3 CFG: DIGOUT3

500

DCTRL−RDY

Terminal X5/A3

4 CFG: DIGOUT4

5003 MCTRL−MMAX

Terminal X5/A4

C0118

0

High active

HIGH level is
active

Inversion of digital output signals,
function block DIGOUT

1

LOW active

LOW level is active

1 DIGOUT1 pol

1

Terminal X5/A1

2 DIGOUT2 pol

1

Terminal X5/A2

3 DIGOUT3 pol

0

Terminal X5/A3

4 DIGOUT4 pol

0

Terminal X5/A4

The digital outputs can be linked with internal digital signals by entering the
selection figure of the internal signal into corresponding subcode of C0117.

Example

ƒ C0117/2 = 505

ð signal source for X5/A2 is the status message

"direction of rotation" (DCTRL−CW/CCW)

ƒ Terminals (X5/A1 ... X5/A4):

– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V

ƒ Response times: 1 ms

In C0118 you can define the active signal level (HIGH level active or LOW level
active) for the terminals X5/A1 ... X5/A4.

Example

ƒ C0118/2 =1

ð With LOW level at X5/A2 the motor rotates in CW

direction (with in−phase motor connection)

Description

Linking signals

Signal level

Inverting the signal level