2 fuses and cable cross-sections, Fuses and cable cross−sections – Lenze EVF9383 User Manual

Page 405

Advertising
background image

Fuses and cable cross−sections

10.2

l

10.2−1

EDSVF9383V EN 7.1−04/2012

10.2

Fuses and cable cross−sections

A DC supply is only possible for the variants V210, V240, V270, V300.

Supply conditions

Range

Description

Mains

DC 480 ... 800 V

Fuses

l

Only semiconductor fuses.

l

If you are using fuses other than those indicated, other fuse currents and
cable cross−sections may result.

Cables

l

DC cables (+U

G

, −U

G

) must always have two−pole insulation.

l

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 40 °C, no bundling of cables or
cores, three loaded cores. The information is a recommendation. Other
designs/laying systems are possible (e.g. according to VDE 0298−4).

Observe all national and regional regulations!

9300

Fuse

Cable cross−section

Quantity

Rated fuse current

Laying system F

+U

G

, −U

G

PE

Type

[A]

[mm

2

]

[mm

2

]

EVF9335−EVV2xx
EVF9335−EVV300

1

400

2 × 50

1)

95

EVF9336−EVV2xx
EVF9336−EVV300

1

400

2 × 50

1)

95

EVF9337−EVV2xx
EVF9337−EVV300

2

350

2 × 95

1)

95

EVF9338−EVV2xx
EVF9338−EVV300

2

400

2 × 95

1)

150

EVF9381−EVV2xx
EVF9381−EVV300

Master

1

400

2 × 50

1)

95

Slave

1

400

2 × 50

1)

95

EVF9382−EVV2xx
EVF9382−EVV300

Master

2

350

2 × 95

1)

95

Slave

2

350

2 × 95

1)

95

EVF9383−EVV2xx
EVF9383−EVV300

Master

2

400

2 × 95

1)

150

Slave

2

400

2 × 95

1)

150

1)

Two conductors per path; both conductors must have the same cross−section

Installation in accordance
with EN 60204−1