Internal motor control with vector control (MCTRL2)

8

8.2
8.2.7

l

8.2−42

EDSVF9383V EN 7.1−04/2012

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−40

C0022 Imax current

à

0

{0.1 A}

− I

max

limit in motor mode

à

depending on C0086

^
6.6−14

C0023 Imax gen.

à

0

{0.1 A}

− I

max

limit in generator mode

à

depending on C0086

^
6.6−14

C0025

s

Feedback type

1

Speed feedback

^ 6.7−1

1

no feedback

No feedback

100

IT (C420) − X8

Input of the
number of
increments in
C0420

Incremental encoder at X8

l

Incremental encoders with TTL
level can only be connected to
X8.

101

IT (C420) − X9

Input of the
number of
increments in
C0420

Incremental encoder at X9

l

Connect incremental encoders
with HTL−level on X9 only

Number of
increments:

Incremental encoder at X8

l

Incremental encoders with TTL
level can only be connected to
X8.

110

IT512−5V

512 inc

111

IT1024−5V

1024 inc

112

IT2048−5V

2048 inc

113

IT4096−5V

4096 inc

C0036 DC brk value

0.0

0.0

{0.1 A}

− Set DC braking current

à

depends on the controller

^
8.2−25

^
8.2−40

C0042 DIS: QSP

Quick stop

l

Display only

^
8.2−25

^
8.2−40

0

QSP inactive

Quick stop is not active

1

QSP active

Quick stop is active

C0050 MCTRL−NSET2

−100.00

{0.01 %}

100.00 Speed setpoint, function block

MCTRL

l

Display of the speed in [%] of
C0011

^
8.2−25

^
8.2−40

C0051 MCTRL−NACT

−36000

{1 rpm}

36000 Actual speed value, function block

MCTRL

l

Read only

^
8.2−25

^
8.2−40

C0052 MCTRL−Umot

0

{1 V}

800 Motor voltage, function block

MCTRL

l

Read only

l

MCTRL−VACT = 100 % = C0090

^
8.2−25

^
8.2−40

C0053 UG−VOLTAGE

0

{1 V}

900 DC−bus voltage, function block

MCTRL

l

Read only

l

MCTRL−DCVOLT = 100 % =
1000 V

^
8.2−25

^
8.2−40

C0054 Imot

0.0

{0.1 A}

5000.0 Actual motor current, function

block MCTRL

l

Read only

l

MCTRL−IACT = 100 % = C0022

^
8.2−25

^
8.2−40