Configuration, Code table – Lenze EVF9383 User Manual

Page 305

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−17

EDSVF9383V EN 4.0−03/2006

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0173

s

UG limit

1

Check during commissioning and
adapt, if necessary!
All controllers in the system must
have the same threshold!

l

Adaptation of UG thresholds

l

Only display in case of the
variants for 400 V mains
(EVF93xx−EV, EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110):
– C0173 = 1
– OU = 700 ... 685 V

^ 12−1

See System
Manual
(extension)

Mains

LU

OU

0

< 400 V

285 V

770 ... 755 V

Device with or without brake
transistor

1

400 V

285 V

770 ... 755 V

2

460 V

328 V

770 ... 755 V

3

480 V

342 V

770 ... 755 V

Device without brake transistor

4

480 V

342 V

800 ... 785 V

Device with brake transistor

5

500 V

342 V

900 ... 885 V

C0174 BR Limit

3

Display of the brake transistor
thresholds
Check during commissioning and
adapt, if necessary!
All controllers connected to the
bus must have the same
threshold!

^ 12−1

See System
Manual
(extension)

Mains

U

BR

OU

0

400 V

685 V

700 V

Only display in case of the variants
for 400 V mains (EVF93xx−EV,
EVF93xx−EVV030,
EVF93xx−EVV060,
EVF93xx−EVV110)

1

400 V / 460 V

755 V

770 V

Only in case of the variants for
400 V/500 V mains
(EVF93xx−EVV210,
EVF93xx−EVV240,
EVF93xx−EVV270,
EVF93xx−EVV300)

2

480 V

785 V

800 V

3

500 V

885 V

900 V

C0178 Op timer

{s}

Display only
Total time of the controller enable
(X5/28 = HIGH)

C0179 mainstimer

{s}

Display only
Total time of mains "ON"

C0182 Ti S−shaped

20.00 0.01

{0.01 s}

50.00 Integration time of S−shaped ramp

function generator, function block
NSET

l

C0182 = 0.00: ramp function
generator operates linearly

l

C0182 > 0.00: ramp function
generator operates in an
S−shape (without jerk)

See System
Manual
(extension)