Update an existing scheduled network, Turn on the power to each chassis, Start rsnetworx for controlnet software – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 100: From the file menu, choose open, Select the file for the network and click open, From the network menu, choose online, Click edits enabled, From the network menu, choose properties, Click ok, From the network menu, choose single pass browse

Advertising
background image

100

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 5

Configure the ControlNet Network

Update an Existing

Scheduled Network

If you are adding the redundant chassis to an existing ControlLogix system that

uses a ControlNet network, complete these steps to update the existing

ControlNet network.

1. Turn on the power to each chassis.
2. Start RSNetWorx for ControlNet software.
3. From the File menu, choose Open.
4. Select the file for the network and click Open.
5. From the Network menu, choose Online.
6. Click Edits Enabled.

7. From the Network menu, choose Properties.
8. In the Network Parameters tab, update the parameters specific to your

system.

9. Click OK.

10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.
12. Click Optimize and re-write schedule for all connections and click OK.

13. Click OK.

You have completed updating your scheduled ControlNet network.

Advertising