Table 48 - alphanumeric error codes, Recovery messages, Table 49 - recover messages – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 235

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

235

Status Indicators

Appendix A

Table 48

describes the alphanumeric codes.

The fault code is a four-character alphanumeric string. Valid characters are 0

9

and A through Z, except S and O. The first character is always E. Each firmware

subsystem within the redundancy module is assigned a range of fault codes. Each

subsystem assigns fault codes within its range.

If you encounter one of these error codes, record the Exxx code and contact

Rockwell Automation Technical Support.

Recovery Messages

For certain faults, the module status display provides recovery instructions. Up to

four, four-character words are displayed.

Table 48 - Alphanumeric Error Codes

Valid Character String

Indication

E

Error.

x

1

The subsystem in which the error was detected.

x

2

The subsystem function or group of functions in which the error was detected.

x

3

The specific error.

Range

Subsystem

Range

Subsystem

E 0 _ _

Back-up Control Object

E C _ _

Object Communication

E 1 _ _

OS Board Support Package

E D _ _

Wall Clock Time Object

E 2 _ _

Chassis Profile Object

E E _ _

Non-maskable Interrupt Service

Routine

E 3 _ _

Coordinated System Time Object

E F _ _

Nonvolatile Storage Object

E 4 _ _

Device Object

E G _ _

RM Fault Handler

E 5 _ _

Extended Log Object

E H _ _

Self Test Object

E 6 _ _

Event Log Object

E I _ _

Workstation Display Object

E 7 _ _

Back-up Communication Object

E J _ _

Industrial Control Platform Object

E 8 _ _

ICP Toolkit

E K _ _

RM Watchdog Manager

E 9 _ _

Indicator Device Driver

E L _ _

Instrumentation Object

E A _ _

RM State Machine

E M _ _

File Object

E B _ _

Event Log Device Driver

Table 49 - Recover Messages

Recovery Instruction Code

Description

RPLC MOD

Replace the module.

RSET MOD

Reset the module.

REMV MOD

Remove the module.

SEAT MOD

Reinsert the module into the chassis.

Advertising