Click the configuration tab in the rmct, Click apply, then click yes – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 254

Advertising
background image

254

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Appendix C

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Step 6: Prepare the Redundant Chassis for the Firmware Upgrade

Complete these steps to prepare both the primary and secondary redundant

chassis for redundancy firmware upgrades.

1. Set the mode switch of the primary and secondary controllers to REM.

If the redundant controllers in both chassis of the redundant chassis pair

are not in Remote Program (REM) mode, the redundancy firmware

upgrade cannot be completed.

2. Open RSLinx Classic software and browse to the redundancy module.
3. Right-click the redundancy module and select Module Configuration to

open the RMCT.

4. Click the Configuration tab in the RMCT.
5. From the Auto-Synchronization pull-down menu, choose Never

.

6. Click Apply, then click Yes.

Advertising