Chapter 7
Program the Redundant Controller
Configure the MSG Instruction
Use the MSG configuration settings that correspond to the command you intend
to issue to the redundancy modules.
Initiate a Switchover
To initiate a switchover, use the MSG instruction parameters listed in this table.
If you need to
See page
Disqualify the Secondary Chassis
Synchronize the Secondary Chassis
Set the Redundancy Module Date and Time
Table 29 - MSG Instruction to Initiate a Switchover
In this tab
Edit this element
To use this value
Configuration
Message Type
CIP Generic
Service Type
Custom
Service Code
4e
Class
bf
Instance
1
Attribute
None - no value needed
Source Element
INT tag with a value of 1
Source Length
2
Destination Element
None - no value needed.
Communication
Path
Browse for the path to the 1756-RM or
1756-RMXT redundancy module.
Connected box
Leave the Connected checkbox unchecked.