Chapter 7

Program the Redundant Controller

Configure the MSG Instruction

Use the MSG configuration settings that correspond to the command you intend

to issue to the redundancy modules.

Initiate a Switchover

To initiate a switchover, use the MSG instruction parameters listed in this table.

If you need to

See page

Initiate a Switchover

172

Disqualify the Secondary Chassis

174

Synchronize the Secondary Chassis

174

Set the Redundancy Module Date and Time

175

Table 29 - MSG Instruction to Initiate a Switchover

In this tab

Edit this element

To use this value

Configuration

Message Type

CIP Generic

Service Type

Custom

Service Code

4e

Class

bf

Instance

1

Attribute

None - no value needed

Source Element

INT tag with a value of 1

Source Length

2

Destination Element

None - no value needed.

Communication

Path

Browse for the path to the 1756-RM or

1756-RMXT redundancy module.

Connected box

Leave the Connected checkbox unchecked.