Design an Enhanced Redundancy System

Communication Modules in Redundant Chassis

Remember these points when placing ControlLogix ControlNet and

EtherNet/IP communication modules in the redundant chassis pair:

You must use enhanced communication modules in enhanced redundancy

systems. Enhanced communication modules contain a ‘2’ in their catalog

number. For example, the 1756-EN2T module.

Standard

ControlNet and EtherNet/IP communication modules are not

supported.

You can use the 1756-EN2TR module only with an enhanced

redundancy system, revision 19.052 or later.

You can use any combination of up to seven enhanced communication

modules in each redundant chassis.

If you use a ControlNet network in your redundant chassis pair, you must

have two ControlNet communication modules outside the redundant

chassis pair. When assigning node address numbers, assign the lowest node

number address to a ControlNet communication module outside the

redundant chassis pair.

For more information, see

Use at Least Four ControlNet Network Nodes

on page 38

through

Assign Lowest Node Numbers to Remote ControlNet

Modules on page 39

.

You cannot use Series A ControlNet communication modules in a

redundancy system.

The Series for EtherNet/IP communication modules is not required to

match in a partnered set. However, if your application requires a feature

specific to a module series level, you must use the same series level for each

module in a partnered set.

For example, only the 1756-EN2T/C communication module only offers

the double-data rate (DDR) feature. You must use 1756-EN2T/C

modules in each chassis of the redundant chassis pair to use DDR.

• Do not use the USB ports of communication modules to access the

redundant system network while the system is running, that is, online.

Using the USB ports while online can result in a loss of communication

after a switchover.

For a list of the ControlLogix communication modules available for use in an

enhanced redundancy system, see

Table 4 on page 24

.