Equation for estimating crossload times, 1756-l6x controllers, 1756-l7x controllers – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual

Page 151

Advertising
background image

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

151

Program the Redundant Controller

Chapter 7

Equation for Estimating Crossload Times

After you have either the size of the last data transfer or the maximum size of data

transferred, use this equation to estimate your controllers’ crossload time for each

program.

1756-L6x Controllers

Crossload time per sync point (ms) = (DINTs  0.00091) + 0.6 ms

1756-L7x Controllers

The following equations apply when a 1756-L7x controller is paired with a

redundancy module in both chassis in a redundancy system.

Table 24 - Crossload Times for 1756-L7x Controllers

Controller

Paired with Redundancy Module

Crossload Time

1756-L7x

1756-RM2/A

Crossload time per sync point (ms) = (DINTs * 0.000275) + 0.54 ms

1756-RM/B

Crossload time per sync point (ms) = (DINTs 0.00043) + 0.3 ms

1756-RM/A

Crossload time per sync point (ms) = (DINTs  0.00091) + 0.6 ms
Where DINTs is the size of the data transferred measured in 4-byte words.

TIP

A sync point is a mechanism that the primary controller uses to keep the
secondary controller in sync. By default, at the end of each program scan, the
primary controller sends the secondary controller the sync point and the

secondary controller responds by moving its execution pointer to match the
primary controller.
The default for phases is not to send a sync point.
Beginning in revision 16.05x, the option exists to manipulate the sync points
for faster program execution.