Click ok, From the network menu, choose single pass browse, From the file menu, choose save – Rockwell Automation 1756-RMxx ControlLogix Enhanced Redundancy System User Manual User Manual
Page 99

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012
99
Configure the ControlNet Network
Chapter 5
8. In the Network Parameters tab, enter the parameters that are appropriate
for your system.
9. Click OK.
10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.
12. Type a name for the file that stores the network configuration, then
click Save.
13. Click Optimize and re-write Schedule for all Connections (default) and
click OK.
You have finished scheduling your new ControlNet network.
Parameter
Specify
Network Update Time (ms)
The minimum repetitive interval when data is sent over the ControlNet
network.
Max Scheduled Address
The highest node number that uses scheduled communication on the
network.
Max Unscheduled Address
The highest node number that you use on the network.
Media Redundancy
The ControlNet channels you are using.
Network Name
A name for identifying the ControlNet network.