Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

281

Enhanced Redundancy System Checklists

Appendix F

Project and Programming Checklist

In addition to the checklist below, see the

ControlLogix Controller Checklist

on

page 279

.

EtherNet/IP HMI

HMI Blind Time is the time during a switchover from primary to secondary, when tag data from the controller is unavailable for reading or writing. See

HMI Blind Time

Reduction on Ethernet During a Switchover on page 21

.

IMPORTANT: This feature requires RSLinx Enterprise software, version 5.50.04 or later.
PanelView Standard terminal

None (the use of the PanelView Standard terminal in a redundant system requires the same considerations as a nonredundant system).

PanelView Plus terminal, VersaView industrial computer running a Windows CE operating system

RSLinx Enterprise software, version 3.0 or later, is used.
Within each of the controllers and communication modules, five connections for each PanelView Plus or VersaView terminal are reserved.

FactoryTalk View SE software with RSLinx Enterprise software

RSLinx Enterprise software, version 3.0 or later is used.
IP address swapping is used.
HMI and both redundant chassis are on the same subnet.

FactoryTalk View SE software with RSLinx software, version 2.x, RSView® 32 software, Any other HMI client software that uses RSLinx software, version 2.x

The number of RSLinx servers that a controller uses is limited to 1…4 (maximum).

(1) Other IP address configurations are permitted, but require additional considerations. For more information, see

Use IP Address Swapping on page 77.

Requirement

Requirement
The Redundancy Module Date and Time has been set by using the RMCT.

One project is created by using RSLogix 5000 software and is downloaded to the primary controller.

(1)

Redundancy is enabled within the Redundancy tab of the Controller Properties dialog box.

Task configuration is either:
One continuous task within the project.
or
Multiple periodic tasks with only one task at the highest priority. Also, multiple tasks are structured so that the fewest possible separate tasks are used.
The redundant controller program does not contain:
Event tasks.

Inhibited tasks.
Programming specific to critical I/O that must be bumpless is placed in the highest-priority user task according to your task configuration.

For 1756-L6x controllers, the task watchdog is (2 * maximum_scan_time) + 150 ms when using ControlNet I/O and (2* maximum_scan_time) + 100 ms when using

Ethernet I/O, where maximum_scan_time is the maximum scan time for the entire task to complete when the redundant controllers are synchronized.
To calculate watchdog time for 1756-L7x controllers, see

Minimum Value for the Watchdog Time on page 177

.

If you use this task structure

Then programming specific to bumpless I/O is in

One continuous task

The continuous task.

One continuous task and one or more periodic tasks

The highest-priority periodic task where only that one task is at the

highest priority.

Multiple periodic tasks

The highest-priority periodic task where only that one task is at the

highest priority.