Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

261

Upgrade from a Standard Redundancy System or to Another Enhanced Redundancy System

Appendix C

The System Update Lock Attempts log indicates when the system lock is

complete.

5. Click Initiate Locked Switchover, then click Yes.

This step results in your secondary chassis assuming control and becoming

the primary chassis. When the switchover is complete, the Locked

Switchover Attempts log indicates success.

In addition to the log, the text in chassis status row indicates the

switchover state.

Once your locked switchover is complete, upgrade the firmware revisions for

modules in the new secondary chassis.

Step 11: Upgrade the New Secondary Chassis Firmware

Complete these steps to upgrade the firmware of all of the modules in the new

secondary chassis, except for the redundancy module that was already upgraded

as described in

Step 7: Upgrade the Primary Chassis Redundancy Module

Firmware on page 255

.

IMPORTANT

Following the locked switchover, secondary controllers no longer contain a user
application and their configuration settings are reset to the factory-default settings.
The new secondary controllers use the default settings and the components in the
secondary chassis are upgraded and the system is synchronized.