208

Rockwell Automation Publication 1756-UM535D-EN-P - November 2012

Chapter 9

Troubleshoot a Redundant System

5. Work back in time (up the lines of preceding events), to locate the point

that a switchover or disqualifying event occurred.

This is the end date and time of the event, and will be indicated on the

Event line in the A chassis event log, with a disqualification code that the

secondary has been disqualified, and a corresponding disqualification code

in the B chassis event log. Again, note that if no secondary is present, you

may not see any secondary disqualification codes in the event log at all. See

Possible Qualification Status Indicators on page 211

.

Preceding events that may indicate the

cause of the switchover.

Chassis A

PwDS and end date and end time in Chassis A.

This is the time the redundancy module

experienced a disqualifying event or switchover.

DSwP and matching end date and end time in

Chassis B. This is the time the redundancy

module experienced a disqualifying event or

switchover.